Cordex logo

Cordex® HP LPS36 line power system

The Cordex® HP LPS36 line power system is a compact, modular DC to DC up converter system designed for distributed power communications applications using ±190VDC (RFT-V circuit) over existing copper network.

select a product's specifications tab

The Cordex® LPS36 line power system packs maximum power into minimum space without compromising on features. A fully equipped 2RU 23-inch shelf includes up to 48 channels. Standard system features include Cordex® CXCi HP controller, front access connection points and connectorized cable output.

Alpha® LPS36 modular DC to DC converter systems incorporate a full range of standard features, including current limiting and individual ground fault interrupt for each circuit. Particular emphasis is placed on recognizing a fault condition and shutting down the circuit as quickly as possible to ensure the highest level of safety. Compliance with GR-1089-CORE -Class A2 enables craftspeople to safely work on the equipment while powered which significantly reduces the administrative, labeling requirements and overhead normally associated with the high voltage wiring.

  • Modular line powering system designed for remotely powering network equipment over twisted copper lines
  • High efficiency >92 percent for reduced operating expense and carbon footprint
  • High temperature tolerance for installation in central office or harsh outside plant cabinet environments
  • Industry leading power density enabling up to 48 channels in a compact 23-inch 2RU form factor
  • High reliability convection-cooled design with optional fan tray
  • Cordex® CXCi HP controller system provides advanced remote web based monitoring and control features
Request a Quote

Product Specification

Take a look at the following Cordex® HP LPS36 line power system product specification:

Product Type

Outdoor Line Power Systems

Application

Small Cells

Macro Cells

Network Access

Passive Optical LANs

Central Offices / Switching Centers

Traffic & Intelligent Transportation Systems (ITS)

Outdoor Small Cells

Input Voltage

-40 to -60Vdc

Output Voltage

±190Vdc

Output Power

96W nominal per output / >92W worst case conditions (4 outputs per module)

Efficiency

>92%

Regulation

<2% no load to full load / <1% line

Dimensions H x W x D (inches)

3.5 x 21.1 x 12.3 / 3.5 x 17.1 x 12.3

Dimensions H x W x D (mm)

88 x 536 x 311 / 88 x 435 x 311

Net Weight (lb)

16 / 12

Net Weight (kg)

7.28 / 5.45

Temperature

Operation with forced air cooling: -40 to 65°C (-40 to 149°F) with mininum cabinet air flow @ 200LFM / Operation with convection cooling: -40 to 45°C (-40 to 122°F) single shelf operation only or separated by 1RU baffle

Humidity

0 to 95% RH non-condensing

Elevation

-500 to 2800m (-1640 to 9186ft)

Heat Dissipation

<118 BTU per hour/module

Connections

Smart Peripherals

Safety

CSA/UL 60950-1 / CSA/UL 60950-21 (RFT-V circuit)

EMC

ETSI 300 386